Voices: Real Answers

What Does NFPA 70E Allow?

FPA 70E Is Tough to Work Through. What Can Somebody Tell Us About This?


We think it makes sense to have zero tolerance for energized work in the panels and MCCs in our new machine designs, since our technicians are more involved in customer-site troubleshooting. NFPA 70E is tough to work through, but it appears we can do things such as restrict high voltage to one enclosure access and employ non-contact test points through the enclosure door and have everything else at 24 V. It seems we then can lock out panels without the technician having to do live-dead-live tests in full PPE. What can somebody tell us about this?

—from January '10 Control Design

ANSWERS

Zero Tolerance
We applaud the zero tolerance policy toward energized work and separating 24 V control circuits from higher working system voltages. Be careful though about using permanently mounted testing methods to determine the presence of voltage. The NFPA 70E technical committee makes it perfectly clear that permanently mounted devices must not be used to confirm the presence or absence of voltage.

Vince Saporita, Vice President, Technical Marketing,
Cooper Bussmann,
www.CooperBussmann.com

Absence of Voltage
I'd rephrase the question. "Can I use an interface (through the door or otherwise) to make absence of voltage tests?"Yes, for an initial test, but no to a through-the-door voltage indicator/test point. You would be relying on an interface and not testing circuits or conductors directly. My dad would always tell me, "Never trust your life to a mechanical device."He was talking about using a hydraulic floor jack without jack stands, but it's great advice for any electrical or mechanical device. The question is not whether they going to fail. The question is "When?"That cannot be answered until the device does fail, and then it's too late. So direct testing for absence of voltage is necessary. Go to the OSHA website and review the Letters of Interpretation.

Unfortunately, there are several companies selling through-the-door voltage detection devices and advertising them as a way around direct contact testing. They are not.

I suggest that you perform a hazard/risk analysis before each testing session/task and carefully evaluate the probability that the upstream protective device would work according to the manufacturer's specifications. If you cannot answer "yes"to that question, it could very well be unsafe to proceed with any type of energized task.

Jim White, Training Director,
Shermco Industries,
www.shermco.com

Sound Practice
The concept of bringing the test point out to a safer access location for technicians makes sense but involves additional costs and change in design.

There are a variety of important issues to recognize and address. Where technicians will be working, it is critical to perform live-dead-live tests on recently energized equipment. That said, the tests ought not to be performed with 24 Vdc as the only connection points, as that does not seem to meet industry standards. When troubleshooting energized equipment, 24 Vdc test points are sound practice.

For lockout-tagout (LOTO) or de-energizing and testing for the absence of voltage, a design that provides a clear line of sight to the potentially energized bus is necessary. This could be accomplished using a Lexan-like material, similar to the IR viewing portals, surrounding the "test point,"ensuring that the bus cannot be contacted by anything: broken part, falling bolt, finger or tool.

To isolate the (600 V class) danger to the inside of an enclosure, while enabling accurate voltage readings from the outside, touch-safe test jacks coupled with bayonet fuse holders that use current-limiting fuses are means toward meeting both the safety and maintenance concerns.

In a preliminary analysis at our facility, the proximity meter we have doesn't detect an energized bus (480 V or 208 V) through an existing panel door. However, placing a ¾-in. sheet of the Mycarta between the proximity tester and insulated, energized cable had no effect; the flux-type tester sensed the voltage correctly. Moving the energized bus close enough to the structure wall—to be sensed through the wall—doesn't seem to be safe and sound practice.

Wallace Tinsley, PSE, Senior Engineer,
Frank Ashley, Specialist-Engineering,
Eaton Electrical,
www.eaton.com

Hazard/Risk
This question points out a widespread issue with many PLCs, control computers, data collection systems and other non-hazardous control equipment that coexist in the same panels as three-phase motor circuits. This requires that all work be performed to the highest hazard/risk category of the panel. Many technicians who program, adjust or troubleshoot such equipment are not necessarily qualified to work in those panels.

The ultimate would be two separate panels. However, a two-door enclosure with a barrier that complies with UL 508A enclosure material and construction requirements, creating two compartments in one enclosure, would provide the equivalent protection. As long as it contains no voltages over 120 V from a typical control transformer circuit, the control compartment would most likely be a Hazard/Risk Category 0, according to NFPA 70E Table 130.7(C)(9), requiring no arc flash PPE. Insulated gloves and/or tools might be required if contact with 120 V is possible. Reducing all voltages to below 50 V should make that compartment electrically non-hazardous, allowing any employee to work on it regardless of qualified status. A full evaluation of the actual panel design is necessary to confirm this.

Benjamin D. Miller, PE, President/Owner,
B. Miller Eng.,
www.bmillerengineering.com

Practical Implementation
NFPA 70E changes both how we design panels and maintain electrical systems. The goal is to find ways to remove voltage exposure for workers. Here are a few practical examples that can be implemented today.

Why open a control panel? What maintenance functions can be moved to the outside of the panel? Through-door data-access ports are more commonplace because they allow programming with the panel door closed. A more recent example is an unmanaged Ethernet switch mounted outside the panel. This unique device allows full through-door access for a worker to troubleshoot and reset the Ethernet switch. What other devices can be reengineered around through-door electrical safety? Perhaps putting certain branch circuit breakers on the outside of the panel is a good application?

For control panel design, providing a physical separation between the power and control compartments within an enclosure might become a standard. Voltages under 50 V are considered safe, so reducing the control power to 24 Vdc makes the control power section safe to work on while it is energized.

Mechanical lockout/tagout (LOTO) procedures requiring electricians to verify zero energy before performing mechanical maintenance needlessly exposes workers to voltage. Since all voltages do not create mechanical motion, through-door voltage checking devices as part of a mechanical LOTO procedure will eliminate voltage exposure. Three-phase voltage indicators (40-750 Vac/30-1000 Vdc) provide visual voltage indication, and through-door voltage portals allow non-contact test points to be used with a non-contact voltage detector.

Philip Allen, President/Owner,
Grace Engineered Products, www.graceport.com


More Voices

What Does NFPA 70E Allow?
03/02/2010
FPA 70E Is Tough to Work Through. What Can Somebody Tell Us About This?

Will Variable Frequency Drives With Standard Induction Motors Give the Same Performance as Stepper Motors?
01/25/2010
Can VFDs Work Like Stepper Motors?: Semiconductor Processing Machinery Looks to Cut Costs With VFD Combination

Is Safety I/O's Fault Detection and Diagnostics Worth the Price?
01/05/2010
Should We Push for Safety I/O?: Does Its Fault Detection and Diagnostics Justify the Cost Hit?

Start Your Motors
12/08/2009
Which Starter Fits the Application?: Expanded Machine Capabilities Might Warrant a Switch From Full-Voltage Starters to VFDs or Soft Starters

Can We Put Old Alarms in HMIs?
11/18/2009
Combining Alarms and HMIs. Is It Possible?

Color Sensing Needs Should Be Considered When Replacing a Machine Vision System
10/07/2009
How Much Color Sensing Is Necessary?: When Should a Slow Machine Vision System Be Replaced by Color Sensors Without Implementing Overkill?

Weigh Hardware and Software Options for Testing I/O Points
09/15/2009
What's Best for Testing I/O Points? Some I/O Is Field-Installed or Requires Actual Production for Responses, so Is Hardware or Software the Best Route?

What Controls Safety?
08/06/2009
What Are the Critical Hardware, Firmware and/or Software Differences between a Safety PLC and a "Regular" PLC?

Fine Art of Fiberoptic Connections
06/17/2009
What Is the Value in Using Fiberoptic Cabling?

Are Single–Speed AC Motors Any Better?
05/06/2009
Is Now a Good Time to Revisit the Motor Market and Seek Improved Solutions

Proximity Switches Get With the Program
04/01/2009
Programmable Sensors Have Their Pluses and Minuses

Which Enclosure When and Where?
02/27/2009
Are There Formulas or Rules-of-Thumb That Must Be Followed When Installing Machines in Explosive Dust and Other Hazardous Areas?

Mix and Match I/O?
02/05/2009
Can I/O from Different Vendors Be Easily Mixed and Matched with One PLC Processor?

Ball Screws, Lead Screws Face Off
01/08/2009
Real-World Differences on Ball screws and Lead Screws

How Can We Reduce the Noise?
11/26/2008
Alternatives to Help Sort Out the Best Course of Action for Resolving Electrical Noise Interference from Motors and Drives That Affect Sensor Signals and HMI

Can Pneumatic Control Be Remote?
10/20/2008
Factors Need to Be Considered When Controlling a Pneumatic Actuator Bank Remotely

How Much Information Is Enough?
09/16/2008
Does More Data Justify the Costs of Replacing Panel Meters?

How Much Safety Is Enough?
09/03/2008
What Level of Safety Is Appropriate for Low-Level Robotics on Metal-Cutting Machines?

Will RTOS Co-exist With GPOS?
07/29/2008

Are PCs Ready for Control and HMI?
06/30/2008
Suggestions on How to Save Some Money and Gain Functionality by Combining Control and HMI into One PC-Based Platform

Control Hydraulic Pumps and Actuators
05/09/2008
Can Hydraulic Pumps and Actuators Be Controlled With the Same Standard PLC?

Digital Upgrade Needs Diagnosis
04/18/2008
A Reader Asks: "Which Handheld Tools Can Techs and Customers Use to Diagnose Digital Networks?"

Which Handheld Technology Is Best?
04/06/2008
A Wireless Mobile Panel Allows Touchscreen Interaction with the Freedom to Move

What Are the Choices on Enclosures?
03/05/2008
Some Experts Offer Alternatives for Machine Enclosures

Can I Measure Up on Color Variation?
02/12/2008
Looking for a Machine Vision System That Will Be Relatively Easy to Design, Install and Maintain?

High Noon for Encoder and Resolver
12/27/2007
Which Should You Use to Measure Speed in Dry Food Packaging Machines?

Wanted: Small-Scale DAQ Solution
10/31/2007
What should you look for in a software package? Tools, wizards, other special features?

Should We Make a Smart Upgrade?
10/04/2007
What are the challenges and benefits of upgrading plastics processing machines instruments from 4-20 mA to smart instruments with digital communications?

I Need Help on Custom Cables
09/11/2007
Should you customize cables and connector assemblies for machine automation applications? If, so where should you go, who can you count on?

Should We Switch to Servos?
08/01/2007
In this installment of The Answer, a reader learns that to achieve accurate positioning using steppers in machine centers they now need to operate more slowly, but are there advantages in changing to AC servos?

I need clean, quiet hydraulics
06/04/2007
In this installment of The Answer, a reader learns how to overcome noise problems and environmental concerns when using hydraulics as the primary source for its metal-forming machines.

Are wireless sensors ready for me?
05/01/2007
A reader wants to know what his best options are for reliable, and easily connectable wireless sensors for vibration monitoring, temperature and presence sensing, and other monitoring and control applications.

We need standards advice
04/09/2007
A reader wants to know what the European and Asian equivalents to UL, NEC, and NFPA are. And what about WEEE and RoHS? Find out the answers and learn where you can go for help regarding standards.

I need a well-supported network
03/08/2007
A reader wants to know what his best options are for finding a control network with sufficient vendor and industry support for multiple sources of controllers, motors, drives, sensors, and components.

We have power-supply problems
02/05/2007
Readers offer up advice on installing redundant, DIN-rail, 24 V, switch-mode power supplies in parallel in this installment of The Answer to Your Problems.


Free Subscriptions

Control Design Digital Edition

Access the entire print issue on-line and be notified each month via e-mail when your new issue is ready for you. Subscribe today.