Foster Transformer's RoHS compliant current transformer

Jan. 23, 2008
Used in motor control applications

RoHS COMPLIANT CURRENT TRANSFORMERS

Line of RoHS compliant current transformers are used in motor control applications, UPS systems, appliances and any other applications where isolated current monitoring is desirable. Standard models feature a 1:500 turns ratio and handle rated currents from 0.1 to 30.0 Amps. Custom designs for other current ranges or ratios are available with a 1000 piece minimum order. Operating frequency range is from 50 Hz to 400 Hz. The transformers have a primary resistance of 0.25 mohm (max) with a secondary resistance of 21 ohm (max). Each size/model includes UL Recognized Class 130 (B) insulation.

Foster Transformer; 513/794-0113; www.foster-transformer.com