Compressor’s surge-control puzzle decoded by testing

Jan. 14, 2020
An engineering study was commissioned to provide a rigorous dynamic simulation of a fractionator and overhead vapor system

An engineering study was commissioned to provide a rigorous dynamic simulation of a fractionator and overhead vapor system. The model was constructed and validated against both steady-state and dynamic plant historical information.

Unreliable compressor controls on a fractionator was causing some issues that a refinery could not figure out. “It was the largest processing unit in the refinery,” said Howard Jemison, PhD, dynamic simulation advisor, Aveva, who shared the story of his investigation at Innovation Days in Austin, Texas. “Especially during startups, there was a problem with the controls. They were looking at the fundamental causes of the trips, as well as whether they might make an improvement in the control system.”

In the configuration, the suction throttle valve (STV) was used to control the overhead on the fractionator. The compressor was more than 400 feet away. “You have a lot of piping, and the anti-surge valve (ASV) was located at the top of the fractionator,” said Jemison. “The pressure was affected almost immediately, and the trips were tied to this pressure.”

Jemison modeled the system to see if it could predict these trips and determine what to do about them.

“When the event happened, it was already past the surge control line, and no action was being taken by the controller,” explained Jemison. “Nobody could give me a satisfactory answer why and how that could happen.”

During startup, the constant-speed compressor would fill with propane, so the molecular weight was lower. “The controller would not take action until the compressor started to surge,” said Jemison. “Then it would take very aggressive action and guarantee it would trip. Once the valve would open, the pressure would go up, and it would trip.”

Jemison decided to investigate a change in the control strategy and run different scenarios. “We had to build a dynamic model of that process and validate against the operation of the actual unit, which is not a trivial exercise,” explained Jemison. “We validated this model against two steady plant conditions, summer and winter. We validated those based on their steady-state models. Now I’ve got the data from the response curves on the performance map, so I had to get to those trip conditions.”

As the reactor would spin up, the compressor would fill with propane. “Somewhere, I’ve got a set of conditions causing this trip,” said Jemison, “but I didn’t have an emulation of the control system they were using. All I cared about was what the valves were doing.“

Jemison took the responses from those valves every 20 milliseconds to see if it matched what he saw from the trends on the live data. Then he tested it by connecting to a Triconex control system.

The two steady-state and two dynamic trip conditions were compared in a detailed model of process scope. “The results from the dynamic validation tests showed the time period was not long,” said Jemison. “The whole thing was over in less than a minute. From the 30-second point, there was a buildup of the pressure, when the reactor was ramping up.”

This client had standardized compressor controls from another site, which Jemison tweaked to match conditions for this site. “Within a week, they’d given me the controls, and they gave me the PT2 file. I tested two different strategies for the fractionator pressure control.”

He tested the STV manipulation on the compressor inlet, which was the existing strategy, and he tested a variable-speed drive (VSD) on the compressor motor.

“We wanted to check this and see if this helped,” said Jemison. “The Triconex showed significant improvement with both of these implementations in avoiding surge or trip conditions altogether. It was a very simple I/O connection from Synsim to the Triconex emulation.”

The VSD had quite a few advantages economically. It could save money over the course of several years, using fewer kW on the compressor, and it was less likely to open the anti-surge valve when running at high rates.

“But, when we went back and ran the conditions that got them into trouble in the first place, the VSD didn’t work well at all,” said Jemison. “It was much more prone to have trouble. The VSD was much slower to respond, especially during that fast ramp-up. The STV actually won the competition because it was already there, so there was no cost to replace it, and because of its better control response in adverse conditions.”

The location of the ASV was at the top of the fractionator. “They wanted to eliminate condensation being blown when it opened,” Jemison explained. “If I want my ASV to respond quickly to upsets in my compressor, I want to minimize the volume downstream of the compressor. If it’s 400 feet away, I don’t have that. We could reduce the discharge volume by 70% by moving that valve, but what did the model say?”

The Triconex controls worked so well it made it hard to go into surge. “I finally found something to delineate these two cases,” said Jemison. “We added a bunch of hydrogen, a low-molecular-weight gas, to push the compressor into surge.”

There were lots and lots of different scenarios we would run. “The two worst ones we wanted to see were power failure and fail-open ASV to see how they’d respond,” said Jemison. “We wanted to be sure we didn’t open any safety valves and avoid these trips.”

The Triconex showed superior performance. “We tried not opening the ASV, and we decided we didn’t need it,” said Jemison.

In the end, the refinery selected Triconex to replace the existing surge control and decided to close the ASV when the compressor trips. Keeping the STV control was the better option, rather than changing to the compressor-motor VSD. They decided to move the ASV from the top of the fractionator to near the compressor and to modify the ASV to be fail-last or fail-closed, rather than fail-open.

Sponsored Recommendations

2024 State of Technology Report: Packaging Equipment

Special considerations and requirements make packaging equipment an interesting vertical market unto itself. This new State of Technology Report from the editors of ...

High Sensitivity Accelerometers to Monitor Traffic and Railroad Vibration for Semiconductor Manufacturing

This paper examines highly sensitive piezoelectric sensors for precise vibration measurement which is critical in semiconductor production to prevent quality and yield issues....

Simulation for Automation Guide

How digital twin solutions are expanding the capabilities of plant engineers.

Enhancing HMI Security and Accessibility with Cloud VPN Solutions

Enhance HMI security and remote access with Beijer’s cloud VPN solution. Enjoy advanced encryption, easy setup, and secure access via laptops, smartphones, or tablets. Cut costs...