How to troubleshoot 4-20 mA analog sensor signals and scaling mismatches
Key Highlights
- A 4 mA "live zero" represents 0% of a sensor's range, allowing 0 mA to signal a broken wire, while readings below 3.6 mA or above 21 mA typically indicate an internal transmitter fault.
- You can measure current non-invasively around a single wire with a process clamp meter, or break the loop, after notifying operations, and measure voltage drop across a precision 250 Ω resistor using Ohm's Law.
- Even a healthy sensor and accurate current signal will display false engineering units if a replacement transmitter's physical range does not match the controller's programmed scaling.
The Starship Morley is quietly cruising along at Warp 2, heading toward a distant M-class planet that the crew is to explore.
Suddenly there is an alarm.
Engineer: “Captain, it seems we are losing pressure on Deck 2. Sensor readings show 15 inches of water column (w.c.).”
Captain: “That cannot be right. Is the sensor faulty?”
Engineer: “It could be that the sensor has failed, but the sensor was just installed.”
Captain: “Determine the cause and correct it.”
This is a common dilemma. There is an analog sensor providing a signal to a controller. How do you know if it is correct?
What is the signal really saying?
A 4-20 mA sensor, also called a transmitter, reports its measurement as a current. Other sensors use voltage or data, but the starship uses 4-20 mA, so we will limit ourselves to that. The bottom of the range is 4 mA, not zero, and the top is 20 mA. That leaves a 16 mA span, so 4 mA means 0% of the sensor’s range and 20 mA means 100% of the sensor’s range. The 4-mA “live zero” is deliberate. A reading of 0 mA cannot be a valid measurement, so it tells you the loop is broken. Many sensors also drive the loop below 3.6 mA or above 21 mA to report an internal fault. Consult the specification sheet for your particular sensor.
Converting current to engineering units uses this formula:
where I = the loop current of the 4-20 mA signal, in mA, and range min and range max come from the sensor. specification sheet, or they may be printed on the sensor body
If you know these values, the expected output can be calculated by hand.
Measuring the loop current
Measurement method depends on what tools are available.
Method 1 uses a standard dc voltmeter and a 250 Ω resistor. This method breaks the loop, so tell operations first. The controller will briefly lose the signal while you work, so place the loop in manual or follow your lockout procedure.
First, measure the loop voltage directly to verify the voltage coming from the power supply. This is typically 24 Vdc. If this is not correct, the power supply may have failed.
If it is correct, disconnect one of the signal wires and connect the resistor in its place, so that the resistor is in series with the loop. Measure the voltage across the resistor with your meter. According to Ohm’s Law, a 4 mA signal through a 250 Ω resistor will measure 1 V, and a 20 mA signal will measure 5 V. To convert your reading to current, divide the voltage by the resistance. For example, 2.2 V across 250 Ω is 8.8 mA. When you are finished, remove the resistor and reconnect the wire.
Get your subscription to Control Design’s daily newsletter.
The result is only as accurate as the resistor, so use a 1% or better part rated for at least 1/4 W, and measure it with your meter before you use it. The resistor adds to the loop’s existing resistance. A larger value such as 500 Ω drops 10 V at 20 mA, which can leave too little voltage for the sensor.
Method 2 uses a process clamp meter. Zero the meter before clamping, following its manual. Then clamp around one wire of the signal pair. The meter measures the current without disrupting the signal, and clamping both wires would read zero. These meters are indispensable for analog signal troubleshooting. The process current reads directly on an LCD screen.
Putting the two together
Let’s use the starship as an example. The engineer reported a sensor reading of 15 inches w.c. The normal reading is 30 inches w.c. He reads the power supply with his voltmeter. It measures the required 24 Vdc. He then uses his process clamp meter to measure the signal. He clamps the meter on one wire and the screen reads 8.8 mA. Knowing that the controller is scaled for a sensor range of 0 to 50 inches w.c., he does the math and arrives at the displayed 15 inches value. The signal is being read correctly, so something else is wrong. He remembers that the sensor was just replaced. A quick check of the sensor reveals the problem. On the body of the sensor the range is listed as 0-100 inches. At that range, 8.8 mA works out to 30 inches, the real pressure. Someone has installed an incorrect sensor. Once the correct sensor ranged 0-50 inches is installed, the alarm clears. The clamp meter now reads 13.62 mA and the pressure reads 30 inches.
Final thoughts
An analog signal is only as meaningful as the range behind it. The controller is scaled to one range, and the sensor must match it. When a reading looks wrong, measure the loop current, do the math by hand and compare the result with the range printed on the sensor. Make that check part of every sensor replacement.
Engineer: “Captain, the alarm is cleared. The replacement sensor had the wrong range.”
Captain: “Well done. Resume course for the M-class planet.”
Understanding what these signals mean and knowing the sensor range and how the controller is scaled will keep your equipment running properly, whether you are a starship engineer or a manufacturing technician.
Read Larry Stepniak’s companion piece, Wolves in the machine: How to verify transducer readings are translated correctly.